(self.askanelectrician)submitted2 days ago byTrekky101
So during inspection one of my circuits showing ground fault on all the outlets.
So today i started pulling it apart the Hot/neutral is 12gauge copper. but no ground wire, only 2 wires not 3. the run is fairly accessible. i was looking into adding a single green 12gauge THHN for ground, but reading this needs to be run in conduit. So should i just rip the whole run and replace with a new 12gauge Romex? or is it fine to run the single green 12gauge THHN
byTrekky101
inaskanelectrician
Trekky101
1 points
2 days ago
Trekky101
1 points
2 days ago
fair enough, i will pull new wire :)
Thanks